1756-IF16H Procurement Questions
How many input channels does the 1756-IF16H provide, and what type are they?
It provides sixteen differential, current inputs, with a dedicated HART modem per channel.
What input current ranges does the module support?
The input range covers 0…20 mA and 4…20 mA.
What is the calibrated accuracy and how often is calibration typically needed?
Calibrated accuracy is better than 0.13% of range (all filters), and the calibration interval is 12 months typical.
Does the isolation rating depend on the module series?
Yes. The catalog record does not pin a series, and the isolation values are carried split: Series A is 50V (continuous), Basic insulation type, Input Channels to Backplane, with no isolation between individual Input Channels; Series B is 250V (continuous), Reinforced Insulation Type, inputs to backplane, with Basic Insulation Type inputs to ground.
What happens on an open circuit input?
Open circuit detection time is a positive full-scale reading within 5 s.
- Inputs
- Sixteen differential, current; Dedicated HART modem per channel
- Input range
- 0…20 mA; 4…20 mA
- Resolution
- 16…21 bits
- Voltage and current ratings
- Series A: Backplane: 5.1V DC @ 200 mA, 24V DC @ 125 mA; Input current range: 0…20 mA, 4…20 mA | Series B: Backplane: 5.1V DC @ 230 mA, 24V DC @ 100 mA; Input current range: 0…20 mA, 4…20 mA
- Total backplane power
- Series A: 4.02 W;; Series B: 3.58 W
- Isolation voltage
- Series A: 50V (continuous), Basic insulation type, Input Channels to Backplane; No isolation between individual Input Channels | Series B: 250V (continuous), Reinforced Insulation Type, inputs to backplane; Basic Insulation Type inputs to ground
- Thermal dissipation
- 12 BTU/hr
- Input impedance
- 249 Ω
- Open circuit detection time
- Positive full-scale reading within 5 s
- Overvoltage protection, max
- 8V DC
- Normal mode noise rejection
- 74 dB @ 50/60 Hz (15 Hz filter); 90 dB @ 60 Hz (20 Hz filter)
- Common mode noise rejection
- Series A: > 90 dB @ 50/60 Hz (15 Hz and 20 Hz filters only);; Series B: > 100 dB @ 50/60 Hz (15 Hz and 20 Hz filters)
- Repeatability
- Better than 0.01% of range (15 Hz and 20 Hz filters only)
- Calibrated accuracy
- Better than 0.13% of range (all filters)
- Calibration interval
- 12 months typical
- Offset drift
- Series A: 27 µV/°C;; Series B: 15PPM/C
- Gain drift with temperature
- 11 ppm/°C
- Module error
- 0.3% of range
- Data format
- IEEE 32-bit floating point
- Input conversion method
- Sigma-Delta
- Module keying
- Electronic, software configurable
- RTB keying
- User-defined mechanical
- Slot width
- 1
- Wire size
- 1756-TBCH Single wire connection: 0.33…2.1 mm2 (22…14 AWG) solid or stranded shielded copper wire rated at 105 °C (221 °F), or greater, 1.2 mm (3/64 in.) insulation max. Double wire connection: 0.33…1.3 mm2 (22…16 AWG) solid or stranded copper wire rated at 105 °C (221 °F), or greater, 1.2 mm (3/64 in.) insulation max. 1756-TBS6H Single wire connection: 0.33…2.1 mm2 (22…14 AWG) solid or stranded shielded copper wire rated at 105 °C (221 °F), or greater, 1.2 mm (3/64 in.) insulation max.
- Wire category
- 2 - on signal ports
- Wire type
- Copper
- Enclosure type rating
- None (open-style)
- Temperature code
- T4
Technical specifications are based on the linked manufacturer references.