1756-IT6I2 Procurement Questions
How many thermocouple inputs does the 1756-IT6I2 provide, and are they isolated?
It provides 6 individually isolated thermocouple inputs with 2 CJC.
Which thermocouple types does this module support?
It supports B, E, J, K, R, S, T, N, C, D, L (TXK/XK) thermocouples, with ITS-90 linearization.
What input ranges and resolution does the module offer?
It offers -12…78 mV at 1.4 µV per bit and -12…30 mV at 0.7 µV per bit on the high resolution range, with 16-bit resolution.
What is the module scan time in different modes?
Module scan time is 25 ms min floating point (millivolt), 50 ms min floating point (temperature), and 10 ms min integer (millivolt).
What isolation voltage does the 1756-IT6I2 provide?
Isolation voltage is 250V (continuous), basic insulation type, input channels-to-backplane and input channel-to-channel, routine tested at 1350V AC for 2 s.
What data formats does the module support?
It supports integer mode (left justified, 2s complement) and IEEE 32-bit floating point.
- Inputs
- 6 individually isolated thermocouple 2 CJC
- Input range
- -12…78 mV (1.4 µV per bit) -12…30 mV (0.7 µV per bit – high resolution range)
- Resolution
- 16 bits -12…78 mV: 1.4 µV/bit -12…30 mV: 0.7 µV/bit
- Thermocouples
- B, E, J, K, R, S, T, N, C, D, L (TXK/XK)
- Thermocouple linearization
- ITS-90
- Current draw @ 5.1V
- 200 mA
- Current draw @ 24V
- 150 mA
- Total backplane power
- 4.6 W
- Power dissipation, max
- 4.6 W
- Thermal dissipation
- 15.7 BTU/hr
- Input impedance
- >10 MΩ
- Open circuit detection time
- Positive full scale reading within 2 s
- Overvoltage protection, max
- 120V AC/DC
- Normal mode noise rejection
- 60 dB at 60 Hz(1)
- Common mode noise rejection
- 160 dB min, tested @ 600V AC/60 Hz applied with 100 Ω differential resistance
- Channel bandwidth
- 15 Hz(1)
- Settling time
- <80 ms to 5% of full scale(1)
- Calibrated accuracy @ 25 °C
- 0.05% of full range @ 25 °C (77 °F) typical Better than 0.1% of range @ 25 °C (77 °F) worst case
- Calibration interval
- 12 months
- Local CJC sensor accuracy
- ±0.3 °C
- Remote CJC sensor accuracy
- ±0.3 °C
- Offset drift
- 0.5 µV/°C
- Gain drift with temperature, nom
- 15 ppm/°C 1.4 µV/°C for -12…78 mV 0.6 µV/°C for -12…30 mV
- Gain drift with temperature, max
- 25 ppm/°C 2.3 µV/°C for -12…78 mV 1.1 µV/°C for -12…30 mV
- Module error
- 0.15% of range
- Module scan time
- 25 ms min floating point (millivolt) 50 ms min floating point (temperature) 10 ms min integer (millivolt)(1)
- Data format
- Integer mode (left justified, 2s complement) IEEE 32-bit floating point
- Module conversion method
- Sigma-Delta
- Isolation voltage
- 250V (continuous), basic insulation type, input channels-to-backplane, and input channel-to-channel Routine tested at 1350V AC for 2 s
- Module keying
- Electronic, software configurable
- RTB keying
- User-defined mechanical
- Slot width
- 1
- Wire category
- 2(2)
- North American temperature code
- T4A
- IEC temperature code
- T4
- Enclosure type
- None (open-style)
Technical specifications are based on the linked manufacturer references.