1756-OF4 Procurement Questions
What output types and ranges does the 1756-OF4 provide?
It provides four voltage or current outputs, with output range covering ±10V and 0…20 mA.
What resolution can I expect on voltage and current outputs?
Voltage resolution is 15 bits across 10.5V (320 µV/bit); current resolution is 16 bits across 21 mA (325 nA/bit).
Does open circuit detection work on both voltage and current outputs?
No. Open circuit detection is for current output only, and the output must be set to >0.1 mA.
What load can the outputs drive?
Drive capability is >2000 Ω for voltage and 0…750 Ω for current.
How is the module keyed and what terminal block keying applies?
Module keying is electronic and software configurable; RTB keying is user-defined mechanical.
What enclosure type and temperature code apply?
The enclosure type is None (open-style) and the temperature code is T4.
- Outputs
- Four voltage or current outputs
- Output range
- ±10V; 0…20 mA
- Resolution
- Voltage: 15 bits across 10.5V, 320 µV/bit; Current: 16 bits across 21 mA, 325 nA/bit
- Voltage and current ratings
- Output voltage: -10…+10V; Output current: 0…20 mA; Backplane: Series A: 5.1V DC, 150 mA max, 24V DC, 120 mA max; Series B: 5.1V DC, 200 mA max, 24V DC, 155 mA max
- Current draw @ 5.1V
- Series A: 150 mA;; Series B: 200 mA max
- Current draw @ 24V
- Series A: 120 mA;; Series B: 155 mA max
- Total backplane power
- Series A: 3.7 W;; Series B: 4.74 W max
- Power dissipation, max
- Series A: 3.7 W, 0...750 ohm load; Series B: 4.74 W, 0...750 ohm load
- Thermal dissipation
- Series A: 10.91 BTU/hr;; Series B: 16.17 BTU/hr
- Open circuit detection
- Current output only (Output must be set to >0.1 mA)
- Overvoltage protection
- Series A: 24V DC;; Series B: ±24V DC
- Short circuit protection
- Electronically current limited to 21 mA or less
- Drive capability
- Voltage: >2000 Ω; Current: 0…750 Ω
- Settling time
- <2 ms to 95% of final value with resistive loads
- Calibrated accuracy
- Better than 0.05% of range from 0…21 mA, -10.4…10.4V
- Calibration interval
- Series A: 12 months typical; Series B: N/A
- Module error
- Series A: Voltage: 0.15% of range; Current: 0.3% of range; Series B: Voltage: 0.1% of range; Current: 0.2% of range
- Module scan time
- 12 ms floating point; 8 ms integer
- Data format
- Integer mode (left justified, 2 s complement); IEEE 32-bit floating point
- Module conversion method
- R-Ladder DAC, monotonicity with no missing codes
- Isolation voltage
- Series A: 250V (continuous), Reinforced insulation type, Output Channels to Backplane No isolation between individual Output Channels;; Series B: 250V (continuous), basic insulation type, output channels to backplane No isolation between individual output channels Compliant and tested according to IEC/UL 61010-1
- Module keying
- Electronic, software configurable
- RTB keying
- User-defined mechanical
- Slot width
- 1
- Wire size
- 1756-TBNH Single wire connection: 0.33…2.1 mm2 (22…14 AWG) solid or stranded copper wire, rated at 105 °C (221 °F) or greater, 1.2 mm (3/64 in.) insulation max. Do not wire more than one conductor on any terminal. Double wire connection: 0.33…1.3 mm2 (22…16 AWG) solid or stranded copper wire, rated at 105 °C (221 °F) or greater, 1.2 mm (3/64 in.) insulation max. Do not wire more than two conductors on any terminal. 1756-TBSH Single wire connection: 0.33…2.1 mm2 (22…14 AWG) solid or stranded shielded copper wire, rated at 105 °C (221 °F) or greater, 1.2 mm (3/64 in.) insulation max. Do not wire more than one conductor on any terminal.
- Wiring category
- 1 - on signal ports
- Enclosure type
- None (open-style)
- Temperature code
- T4
Technical specifications are based on the linked manufacturer references.
What Does Our Clients Say
Mitsubishi MR-J4
Laura Navas
Great product!
2019/12/01
Keyence sensor
EQDR SALES
Original and fast!
2020/02/22