Allen-Bradley 1756-OF8 ControlLogix analog voltage/current output module

Series#: AllenBradley

Product Details

  • Allen-Bradley 1756-OF8 ControlLogix analog voltage/current output module
  • Device type: ControlLogix analog voltage/current output module; Channels / wiring: 8 voltage/current outputs
  • Channel isolation: No isolation between individual output channels

Specification

Allen-Bradley 1756-OF8 — ControlLogix analog voltage/current output module.

Technical Specifications

SpecificationDetails
ManufacturerAllen-Bradley
Catalog number1756-OF8
Device typeControlLogix analog voltage/current output module
Channels / wiring8 voltage/current outputs
Channel isolationNo isolation between individual output channels

Ordering & Compatibility

Do not treat the standard OF8 as eight independently isolated outputs.

Match the complete catalog number, hardware series, installed configuration and required accessories before ordering. Unit condition, package contents, delivery and warranty must be confirmed in the quotation.

1756-OF8 Procurement Questions

What output ranges does the 1756-OF8 support?

The module provides eight voltage or current outputs, with an output range of ±10V and 0…20 mA.

What load can the outputs drive?

Drive capability is >2000 Ω for voltage output and 0…750 Ω for current output.

How is open circuit detected?

Open circuit detection applies to current output only, and the output must be set to >0.1 mA.

What data formats does the module support?

Data format is integer mode (left justified, 2 s complement) and IEEE 32-bit floating point.

What is the minimum module scan time?

The minimum module scan time is 12 ms in floating point and 8 ms in integer mode.

Outputs
Eight voltage or current outputs
Output range
±10V; 0…20 mA
Resolution
Voltage: 15 bits across 10.5V, 320 µV/bit; Current: 16 bits across 21 mA, 325 nA/bit
Current draw @ 5.1V
Series A: 150 mA;; Series B: 200 mA
Current draw @ 24V
Series A: 210 mA;; Series B: 300 mA
Total backplane power
Series A: 5.8 W; Series B: 8.22 W
Voltage and current ratings
Output Voltage: -10…+10V; Output Current: 0…20 mA; Backplane: Series A: 5.1V DC, 150 mA max, 24V DC, 210 mA max; Series B: 5.1V DC, 200 mA max, 24V DC, 300 mA max
Power dissipation
Series A: 5.8 W, 0...750 ohm loads; Series B: 8.22 W, 0...750 ohm loads
Thermal dissipation
Series A: 16.78 BTU/hr;; Series B: 28.03 BTU/hr
Open circuit detection
Current output only (Output must be set to >0.1 mA)
Overvoltage protection
Series A: 24V DC;; Series B: ± 24V DC
Short circuit protection
Electronically current limited to 21 mA or less
Drive capability
Voltage: >2000 Ω; Current: 0…750 Ω
Settling time
< 2 ms to 95% of final value with resistive loads
Calibrated accuracy @ 25 °C (77 °F)
Better than 0.05% of range from 0…21 mA, -10.4…10.4V
Calibration interval
Series A: 12 months typical; Series B: N/A
Module error
Series A: Voltage: 0.15% of range; Current: 0.3% of range; Series B: Voltage: 0.1% of range; Current: 0.2% of range
Module scan time, min
12 ms floating point; 8 ms integer
Data format
Integer mode (left justified, 2 s complement) IEEE 32-bit floating point
Module conversion method
R-Ladder DAC, monotonicity with no missing codes
Isolation voltage
Series A: 250V (continuous), Reinforced insulation type, Output Channels to Backplane No isolation between individual Output Channels;; Series B: 250V (continuous), basic insulation type, Output Channels to Backplane No isolation between individual output channels Compliant and tested according to IEC/UL 61010-1
Module keying
Electronic, software configurable
RTB keying
User-defined mechanical
Slot width
1
Wire size
1756-TBNH Single wire connection: 0.33…2.1 mm2 (22…14 AWG) solid or stranded copper wire, rated at 105 °C (221 °F) or greater, 1.2 mm (3/64 in.) insulation max. Do not wire more than one conductor on any terminal. Double wire connection: 0.33…1.3 mm2 (22…16 AWG) solid or stranded copper wire, rated at 105 °C (221 °F) or greater, 1.2 mm (3/64 in.) insulation max. Do not wire more than two conductors on any terminal 1756-TBSH Single wire connection, 0.33…2.1 mm2 (22…14 AWG) solid, or stranded shielded copper wire rated at 105 °C (221 °F), or greater, 1.2 mm (3/64 in.) insulation max. Do not wire multiple conductors on any terminal
Wiring category
1 - on signal ports
Enclosure type
None (open-style)
Temperature code
T4

Technical specifications are based on the linked manufacturer references.

Unmatched Customer Service

After Hours Shipping

Real Time Order Tracking

Flexible Delivery Options

Intact Technical Supports

What Does Our Clients Say

Mitsubishi MR-J4

Laura Navas

Great product!

2019/12/01

Keyence sensor

EQDR SALES

Original and fast!

2020/02/22

Need Professional Tech Support or a Quote?

  • Our senior engineers provide 1-on-1 selection & configuration advice
  • 100% genuine products guaranteed with rapid global delivery
UP
WhatsApp