Allen-Bradley 1756-CFM — ControlLogix configurable flowmeter module.
| Specification | Details |
|---|---|
| Manufacturer | Allen-Bradley |
| Catalog number | 1756-CFM |
| Device type | ControlLogix configurable flowmeter module |
| Channels / wiring | 4 inputs (2 per channel), 2 current-sourcing outputs |
Do not order a flowmeter module as a passive chassis filler.
Match the complete catalog number, hardware series, installed configuration and required accessories before ordering. Unit condition, package contents, delivery and warranty must be confirmed in the quotation.
The module has 4 inputs (2 per channel). Two flowmeter (F) inputs are used for all modes, and 2 gate inputs are used in Totalizer mode for prover/store count.
High resolution, max is 100 kHz, and the frequency specification is 0.0005 Hz resolution.
Yes, totalizer fill and prover is supported. Gate inputs are used in Totalizer mode for prover/store count.
The module has 2 current sourcing outputs, and reverse polarity protection applies to outputs only.
Isolation voltage is 250V (continuous), reinforced insulation type, I/O to backplane; 250V (continuous), basic insulation type, I/O group to group; compliant and tested according to IEC/UL 61010-1.
Module keying is electronic and software configurable, RTB keying is user-defined mechanical, and screw torque is 0.5 N•m (4.4 lb•in).
Technical specifications are based on the linked manufacturer references.