1794-OA8 Procurement Questions
Which terminal base units can be used with the 1794-OA8?
The listed terminal base units are 1794-TBN, 1794-TBNF, 1794-TB2, 1794-TB3, 1794-TB3S, 1794-TBKD, 1794-TBNK, 1794-TB3K and 1794-TB3SK.
What on-state output current can the 1794-OA8 carry at elevated ambient temperature?
The maximum is 500 mA per output @ 55 °C; 750 mA per output @ 35 °C; 1.0 A on 4 nonadjacent outputs and 500 mA on the remaining 4 outputs @ 30 °C.
How much off-state leakage current should be expected from the 1794-OA8 outputs?
The maximum off-state output leakage current is 2.25 mA.
What surge current can the 1794-OA8 outputs handle?
The maximum output surge current is 7 A for 45 ms, repeatable every 8 s.
What fusing is recommended for the 1794-OA8 outputs?
Use a 1.6 A, 250V slow-blow fuse (Littelfuse part number 23901.6; San-o SD6-1.6 A, AB part number 94171304); the 1794-TBNF comes with SD6-1.6 A fuses installed.
What is the operating temperature range of the 1794-OA8?
The operating temperature range is -20…+55 °C (-4…+131 °F).
- Voltage, on-state output, nom
- 120V AC
- Terminal base unit
- 1794-TBN, 1794-TBNF, 1794-TB2, 1794-TB3, 1794-TB3S, 1794-TBKD, 1794-TBNK, 1794-TB3K, 1794-TB3SK
- Current, on-state output, min
- 5 mA per output
- Current, on-state output, max
- 500 mA per output @ 55 °C; 750 mA per output @ 35 °C; 1.0 A on 4 nonadjacent outputs and 500 mA on the remaining 4 outputs @ 30 °C
- Current, on-state output, per module
- 4.0 A (8 outputs @ 500 mA)
- Leakage current, off-state output, max
- 2.25 mA
- Voltage drop, on-state output, max
- 1.0V @ 0.5 A
- Output surge current, max
- 7 A for 45 ms, repeatable every 8 s
- Voltage, on-state output, min
- 85V AC
- Voltage, on-state output, max
- 132V AC
- Power dissipation, max
- 4.1 W @ 0.5 A; 6.3 W @ 0.75 A; 6.3 W @ 1.0 A
- Thermal dissipation, max
- 14.0 BTU/hr @ 0.5 A; 21.1 BTU/hr @ 0.75 A; 21.4 BTU/hr @ 1.0 A
- Dimensions (HxWxD), approx
- 46 x 94 x 53 mm (1.8 x 3.7 x 2.1 in); 94 x 94 x 69 mm (3.7 x 3.7 x 2.7 in) installed
- Isolation voltage
- 120V (continuous), I/O to system; no isolation between individual channels; tested to 2150V DC for 1 s and 1250V AC for 60 s
- Temperature, operating
- -20…+55 °C (-4…+131 °F)
- Recommended output fusing
- 1.6 A, 250V slow-blow fuse (Littelfuse part number 23901.6; San-o SD6-1.6 A, AB part number 94171304); the 1794-TBNF comes with SD6-1.6 A fuses installed