Allen-Bradley 1794-OA8I FLEX I/O Digital Output Module

Series#: AllenBradley

Product Details

  • Allen-Bradley 1794-OA8I FLEX I/O Digital Output Module
  • Inputs: 0
  • Outputs: 8
  • Electrical category: 120V AC

Specification

Allen-Bradley 1794-OA8I FLEX I/O Digital Output Module.

Technical Specifications

SpecificationDetails
ManufacturerAllen-Bradley
Catalog number1794-OA8I
Inputs0
Outputs8
Electrical category120V AC
I/O arrangementIsolated outputs
Listed terminal bases1794-TBNF, 1794-TB2, 1794-TB3, 1794-TB3S, 1794-TBN, 1794-TBKD, 1794-TB3K, 1794-TB3SK, 1794-TBNK

1794-OA8I Procurement Questions

What on-state output current can the 1794-OA8I carry, and does it depend on temperature?

The maximum on-state output current is 500 mA per output @ 55 °C, 750 mA per output @ 35 °C, and 1.0 A on 4 nonadjacent outputs and 500 mA on the remaining 4 outputs @ 30 °C; the minimum on-state output current is 5 mA per output.

What is the total on-state output current per module?

The on-state output current per module is 4.0 A (8 outputs @ 500 mA).

What isolation does the 1794-OA8I provide?

Isolation voltage is 120V (continuous), I/O to system (and channel to channel for 1794-OA8I); there is no isolation between individual channels; it is tested to 2150V DC for 1 s and 1250V AC for 60 s.

Which terminal base units can the 1794-OA8I be used with?

The terminal base units are 1794-TBN, 1794-TBNF, 1794-TB2, 1794-TB3, 1794-TB3S, 1794-TBKD, 1794-TBNK, 1794-TB3K, 1794-TB3SK.

What output fusing is recommended for the 1794-OA8I?

Use a 1.6 A, 250V slow-blow fuse (Littelfuse part number 23901.6; San-o SD6-1.6 A, AB part number 94171304); the 1794-TBNF comes with SD6-1.6 A fuses installed.

What is the maximum output surge current and how often can it repeat?

The maximum output surge current is 7 A for 45 ms, repeatable every 8 s.

Voltage, on-state output, nom
120V AC
Terminal base unit
1794-TBN, 1794-TBNF, 1794-TB2, 1794-TB3, 1794-TB3S, 1794-TBKD, 1794-TBNK, 1794-TB3K, 1794-TB3SK
Current, on-state output, min
5 mA per output
Current, on-state output, max
500 mA per output @ 55 °C; 750 mA per output @ 35 °C; 1.0 A on 4 nonadjacent outputs and 500 mA on the remaining 4 outputs @ 30 °C
Current, on-state output, per module
4.0 A (8 outputs @ 500 mA)
Leakage current, off-state output, max
2.25 mA
Voltage drop, on-state output, max
1.0V @ 0.5 A
Output surge current, max
7 A for 45 ms, repeatable every 8 s
Voltage, on-state output, min
85V AC
Voltage, on-state output, max
132V AC
Power dissipation, max
4.1 W @ 0.5 A; 6.3 W @ 0.75 A; 6.3 W @ 1.0 A
Thermal dissipation, max
14.0 BTU/hr @ 0.5 A; 21.1 BTU/hr @ 0.75 A; 21.4 BTU/hr @ 1.0 A
Dimensions (HxWxD), approx
46 x 94 x 53 mm (1.8 x 3.7 x 2.1 in); 94 x 94 x 69 mm (3.7 x 3.7 x 2.7 in) installed
Isolation voltage
120V (continuous), I/O to system (and channel to channel for 1794-OA8I); no isolation between individual channels; tested to 2150V DC for 1 s and 1250V AC for 60 s
Temperature, operating
-20…+55 °C (-4…+131 °F)
Recommended output fusing
1.6 A, 250V slow-blow fuse (Littelfuse part number 23901.6; San-o SD6-1.6 A, AB part number 94171304); the 1794-TBNF comes with SD6-1.6 A fuses installed

Technical specifications are based on the linked manufacturer reference.

Unmatched Customer Service

After Hours Shipping

Real Time Order Tracking

Flexible Delivery Options

Intact Technical Supports

What Does Our Clients Say

Mitsubishi MR-J4

Laura Navas

Great product!

2019/12/01

Keyence sensor

EQDR SALES

Original and fast!

2020/02/22

Need Professional Tech Support or a Quote?

  • Our senior engineers provide 1-on-1 selection & configuration advice
  • 100% genuine products guaranteed with rapid global delivery
UP
WhatsApp