1794-IB10XOB6 Procurement Questions
Which terminal base units can be used with the 1794-IB10XOB6?
The published terminal base units for this module are 1794-TB2, 1794-TB3, 1794-TB3S, 1794-TB3K and 1794-TB3SK.
Do the outputs of the 1794-IB10XOB6 need external fusing?
Yes. Module outputs are not fused, and external fusing for individual outputs is required.
What is the maximum output current per channel and per module?
The on-state output maximum is 2.0 A per channel and 10 A per module.
What external DC supply voltage range does the module accept?
The external DC supply voltage range is 10…31.2V DC, which includes 5% AC ripple.
What is the operating temperature range of the 1794-IB10XOB6?
The operating temperature range is -20…+55 °C (-4…+131 °F).
How is the 1794-IB10XOB6 isolated between field side and system?
Isolation is 50V (continuous), Basic Insulation Type, type tested at 1250V AC for 60 s and routine tested at 2121V DC for 1 s, between field side and system; there is no isolation between individual channels.
- Terminal base unit
- 1794-TB2, 1794-TB3, 1794-TB3S, 1794-TB3K, 1794-TB3SK
- Isolation voltage
- 50V (continuous), Basic Insulation Type; type tested at 1250V AC for 60 s, between field side and system; routine tested at 2121V DC for 1 s, between field side and system; no isolation between individual channels
- Power dissipation, max
- 6.0 W @ 31.2V DC
- Thermal dissipation, max
- 20.3 BTU/hr @ 31.2V DC
- Number of inputs
- 10
- Voltage, on-state input, min
- 10V DC
- Voltage, on-state input, nom
- 24V DC
- Voltage, on-state input, max
- 31.2V DC
- Current, on-state input, min
- 2.0 mA
- Current, on-state input, nom
- 8.0 mA @ 24V DC
- Current, on-state input, max
- 11.0 mA
- Voltage, off-state input, max
- 5V DC
- Current, off-state input, max
- 1.5 mA
- Input impedance, max
- 4.8 kΩ
- Number of outputs
- 6
- Voltage, on-state output, min
- 10V DC
- Voltage, on-state output, nom
- 24V DC
- Voltage, on-state output, max
- 31.2V DC
- Voltage drop, on-state output, max
- 1V DC @ 2 A; 0.5V DC @ 1 A
- Current, on-state output, min
- 1.0 mA per channel
- Current, on-state output, max
- 2.0 A per channel; 10 A per module
- External fusing
- Module outputs are not fused; external fusing for individual outputs is required
- Voltage, off-state output, max
- 31.2V DC
- Leakage current, off-state output, max
- 0.5 mA
- Output delay time, OFF to ON, max
- 0.5 ms
- Output delay time, ON to OFF, max
- 1.0 ms
- Output surge current, max
- 4 A for 50 ms, repeatable every 2 s
- Dimensions (HxWxD), approx
- 46 x 94 x 53 mm (1.8 x 3.7 x 2.1 in); 94 x 94 x 69 mm (3.7 x 3.7 x 2.7 in) installed
- External DC supply voltage range
- 10…31.2V DC (includes 5% AC ripple)
- External DC supply current range
- 8 mA @ 10V DC; 15 mA @ 19.2V DC; 19 mA @ 24V DC; 25 mA @ 31.2V DC
- Temperature, operating
- -20…+55 °C (-4…+131 °F)
Technical specifications are based on the linked manufacturer reference.