Allen-Bradley 1794-OB8 FLEX I/O Digital Output Module

Series#: AllenBradley

Product Details

  • Allen-Bradley 1794-OB8 FLEX I/O Digital Output Module
  • Inputs: 0
  • Outputs: 8
  • Electrical category: 24V DC

Specification

Allen-Bradley 1794-OB8 FLEX I/O Digital Output Module.

Technical Specifications

SpecificationDetails
ManufacturerAllen-Bradley
Catalog number1794-OB8
Inputs0
Outputs8
Electrical category24V DC
I/O arrangementNonisolated outputs
Listed terminal bases1794-TB2, 1794-TB3, 1794-TB3S, 1794-TB3K, 1794-TB3SK

1794-OB8 Procurement Questions

What external DC supply voltage and current does the 1794-OB8 require?

The external DC supply voltage range is 10…31.2V DC (5% ripple), and the external DC supply current range is 10…35 mA.

How much current can each output channel and the module handle?

The on-state output current is a minimum of 1.0 mA per channel and a maximum of 500 mA per channel, with 4 A per module.

Which terminal base units can the 1794-OB8 be used with?

It is listed for the 1794-TB2, 1794-TB3, 1794-TB3S, 1794-TB3K, and 1794-TB3SK terminal base units.

Are the module outputs fused, and what external fuse is recommended?

The module outputs are not fused, and external fusing is strongly recommended; the recommended external fuse is the SAN-O MQ4-800 mA fuse.

What isolation does the 1794-OB8 provide between I/O and the system?

Isolation is 50V continuous, I/O to system, tested to 850V DC for 1 s, I/O to system; there is no isolation between individual channels.

What are the output delay times for the 1794-OB8?

The maximum output delay time is 0.5 ms OFF to ON and 1.0 ms ON to OFF.

Voltage, on-state output, nom
24V DC, sourcing
Voltage, on-state output, min
10V DC
Voltage, on-state output, max
31.2V DC
Voltage drop, on-state output, max
0.5V DC
Terminal base unit
1794-TB2, 1794-TB3, 1794-TB3S, 1794-TB3K, 1794-TB3SK
Current, on-state output, min
1.0 mA per channel
Current, on-state output, max
500 mA per channel; 4 A per module
Leakage current,
0.5 mA
Output surge current, max
2 A for 50 ms, repeatable every 2 s
Output delay time, OFF to ON, max
0.5 ms
Output delay time, ON to OFF, max
1.0 ms
External DC supply voltage range
10…31.2V DC (5% ripple)
External DC supply current range
10…35 mA
Power dissipation, max
3.3 W @ 31.2V DC
Thermal dissipation, max
11.2 BTU/hr @ 31.2V DC
Dimensions (HxWxD), approx
46 x 94 x 53 mm (1.8 x 3.7 x 2.1 in); 94 x 94 x 69 mm (3.7 x 3.7 x 2.7 in) installed
Isolation voltage
50V continuous, I/O to system; tested to 850V DC for 1 s, I/O to system; no isolation between individual channels
Temperature, operating
-20…+55 °C (-4…+131 °F)
Recommended external fusing
SAN-O MQ4-800 mA fuse (module outputs are not fused; external fusing is strongly recommended)

Technical specifications are based on the linked manufacturer reference.

Unmatched Customer Service

After Hours Shipping

Real Time Order Tracking

Flexible Delivery Options

Intact Technical Supports

What Does Our Clients Say

Mitsubishi MR-J4

Laura Navas

Great product!

2019/12/01

Keyence sensor

EQDR SALES

Original and fast!

2020/02/22

Need Professional Tech Support or a Quote?

  • Our senior engineers provide 1-on-1 selection & configuration advice
  • 100% genuine products guaranteed with rapid global delivery
UP
WhatsApp