1794-OB16 Procurement Questions
What supply voltage does the 1794-OB16 require?
The external DC supply voltage range is 10…31.2V DC (5% ripple), and the external DC supply current range is 20…65 mA.
How much current can each output channel and the module carry?
The maximum on-state output current is 500 mA per channel and 8 A per module, while the minimum on-state output current is 1.0 mA per channel.
Which terminal base units can be used with this module?
The listed terminal base units are 1794-TB2, 1794-TB3, 1794-TB3S, 1794-TB3K and 1794-TB3SK.
Are the module outputs fused, and what external fusing is recommended?
Module outputs are not fused and external fusing is strongly recommended; the recommended external fuse is the SAN-O MQ4-800 mA fuse.
What are the output switching delays?
The maximum output delay time is 0.5 ms OFF to ON and 1.0 ms ON to OFF.
What operating temperature range applies?
The operating temperature range is -20…+55 °C (-4…+131 °F).
- Voltage, on-state output, nom
- 24V DC, sourcing
- Voltage, on-state output, min
- 10V DC
- Voltage, on-state output, max
- 31.2V DC
- Voltage drop, on-state output, max
- 0.5V DC
- Terminal base unit
- 1794-TB2, 1794-TB3, 1794-TB3S, 1794-TB3K, 1794-TB3SK
- Current, on-state output, min
- 1.0 mA per channel
- Current, on-state output, max
- 500 mA per channel; 8 A per module
- Leakage current,
- 0.5 mA
- Output surge current, max
- 2 A for 50 ms, repeatable every 2 s
- Output delay time, OFF to ON, max
- 0.5 ms
- Output delay time, ON to OFF, max
- 1.0 ms
- External DC supply voltage range
- 10…31.2V DC (5% ripple)
- External DC supply current range
- 20…65 mA
- Power dissipation, max
- 5.3 W @ 31.2V DC
- Thermal dissipation, max
- 18.1 BTU/hr @ 31.2V DC
- Dimensions (HxWxD), approx
- 46 x 94 x 53 mm (1.8 x 3.7 x 2.1 in); 94 x 94 x 69 mm (3.7 x 3.7 x 2.7 in) installed
- Isolation voltage
- 50V continuous, I/O to system; tested to 850V DC for 1 s, I/O to system; no isolation between individual channels
- Temperature, operating
- -20…+55 °C (-4…+131 °F)
- Recommended external fusing
- SAN-O MQ4-800 mA fuse (module outputs are not fused; external fusing is strongly recommended)