1794-OB16D Procurement Questions
What external DC supply voltage range does the 1794-OB16D require?
The external DC supply voltage range is 10…31.2V DC (5% AC ripple), and the external DC supply current range is 56…78 mA.
What is the maximum on-state output current per channel and per module?
The on-state output current maximum is 500 mA per channel and 8 A per module; the minimum is 2.0 mA per channel.
How does the module protect against short circuits?
Short circuit protection is thermal shutdown (auto reset).
What isolation does the 1794-OB16D provide?
Isolation voltage is 50V continuous, I/O to system, tested to 2121V DC for 1 s, I/O to system; there is no isolation between individual channels.
Which terminal base units can be used with this module?
The terminal base unit options are 1794-TB3, 1794-TB3S, 1794-TB3K, and 1794-TB3SK.
What are the operating temperature limits and maximum power dissipation?
Operating temperature is 0…55 °C (32…131 °F); maximum power dissipation is 4.8 W @ 31.2V DC and maximum thermal dissipation is 16.4 BTU/hr @ 31.2V DC.
- Voltage, on-state output, min
- 10V DC, sinking
- Voltage, on-state output, max
- 31.2 V DC
- Voltage drop, on-state output, max
- 0.5V DC @ 0.5 A
- Terminal base unit
- 1794-TB3, 1794-TB3S, 1794-TB3K, 1794-TB3SK
- Current, on-state output, min
- 2.0 mA per channel
- Current, on-state output, max
- 500 mA per channel; 8 A per module
- Leakage current, off-state output, max
- 0.5 mA
- Output surge current, max
- 2 A for 50 ms, repeatable every 2 s
- External DC supply voltage range
- 10…31.2V DC (5% AC ripple)
- External DC supply current range
- 56…78 mA
- Power dissipation, max
- 4.8 W @ 31.2V DC
- Thermal dissipation, max
- 16.4 BTU/hr @ 31.2V DC
- Short circuit protection
- Thermal shutdown (auto reset)
- Open wire detection, off-state leakage current
- 0.1 mA
- Detect reverse polarity voltage, min
- 10V
- Dimensions (HxWxD), approx
- 46 x 94 x 53 mm (1.8 x 3.7 x 2.1 in); 94 x 94 x 69 mm (3.7 x 3.7 x 2.7 in) installed
- Isolation voltage
- 50V continuous, I/O to system; tested to 2121V DC for 1 s, I/O to system; no isolation between individual channels
- Temperature, operating
- 0…55 °C (32…131 °F)
Technical specifications are based on the linked manufacturer reference.