1794-OC16 Procurement Questions
Which terminal base units can be used with the 1794-OC16?
The listed terminal base units are 1794-TB2, 1794-TB3, 1794-TB3S, 1794-TB3K and 1794-TB3SK.
What external DC supply voltage and current does the 1794-OC16 require?
The external DC supply voltage range is 30…60V DC (5% ripple), and the external DC supply current range is 13…27 mA.
What are the on-state output voltage limits of the 1794-OC16?
The nominal on-state output voltage is 48V DC, sourcing; the minimum is 30V DC; the maximum is 60V DC @ 45 °C and 55V DC @ 55 °C.
How much current can each channel and the whole module deliver?
The on-state output current is 2.0 mA per channel minimum, with a maximum of 500 mA per channel and 8 A per module.
What isolation does the 1794-OC16 provide?
Isolation is 75V continuous, I/O to system, tested to 1900V DC for 1 s, I/O to system; there is no isolation between individual channels.
What external fusing is recommended for the 1794-OC16?
A 2 A, 150V AC MQ2 normal fuse is recommended; module outputs are not fused, and external fusing is strongly recommended.
- Voltage, on-state output, nom
- 48V DC, sourcing
- Voltage, on-state output, min
- 30V DC
- Voltage, on-state output, max
- 60V DC @ 45 °C; 55V DC @ 55 °C
- Voltage drop, on-state output, max
- 1.0V DC @ 0.5 A
- Terminal base unit
- 1794-TB2, 1794-TB3, 1794-TB3S, 1794-TB3K, 1794-TB3SK
- Current, on-state output, min
- 2.0 mA per channel
- Current, on-state output, max
- 500 mA per channel; 8 A per module
- Leakage current,
- 1.0 mA
- Output surge current, max
- 4 A for 10 ms, repeatable every 2 s
- Output delay time, OFF to ON, max
- 0.5 ms
- Output delay time, ON to OFF, max
- 1.0 ms @ 25 °C; 2.0 ms @ 55 °C
- External DC supply voltage range
- 30…60V DC (5% ripple)
- External DC supply current range
- 13…27 mA
- Power dissipation, max
- 3.7 W @ 60V DC
- Thermal dissipation, max
- 12.6 BTU/hr @ 60V DC
- Dimensions (HxWxD), approx
- 46 x 94 x 53 mm (1.8 x 3.7 x 2.1 in); 94 x 94 x 69 mm (3.7 x 3.7 x 2.7 in) installed
- Isolation voltage
- 75V continuous, I/O to system; tested to 1900V DC for 1 s, I/O to system; no isolation between individual channels
- Temperature, operating
- 0…55 °C (32…131 °F)
- Recommended external fusing
- 2 A, 150V AC MQ2 normal fuse (module outputs are not fused; external fusing is strongly recommended)