Allen-Bradley 1794-OC16 FLEX I/O Digital Output Module

Series#: AllenBradley

Product Details

  • Allen-Bradley 1794-OC16 FLEX I/O Digital Output Module
  • Inputs: 0
  • Outputs: 16
  • Electrical category: 48V DC

Specification

Allen-Bradley 1794-OC16 FLEX I/O Digital Output Module.

Technical Specifications

SpecificationDetails
ManufacturerAllen-Bradley
Catalog number1794-OC16
Inputs0
Outputs16
Electrical category48V DC
I/O arrangementNonisolated outputs
Listed terminal bases1794-TB3, 1794-TB3S, 1794-TB3K, 1794-TB3SK

1794-OC16 Procurement Questions

Which terminal base units can be used with the 1794-OC16?

The listed terminal base units are 1794-TB2, 1794-TB3, 1794-TB3S, 1794-TB3K and 1794-TB3SK.

What external DC supply voltage and current does the 1794-OC16 require?

The external DC supply voltage range is 30…60V DC (5% ripple), and the external DC supply current range is 13…27 mA.

What are the on-state output voltage limits of the 1794-OC16?

The nominal on-state output voltage is 48V DC, sourcing; the minimum is 30V DC; the maximum is 60V DC @ 45 °C and 55V DC @ 55 °C.

How much current can each channel and the whole module deliver?

The on-state output current is 2.0 mA per channel minimum, with a maximum of 500 mA per channel and 8 A per module.

What isolation does the 1794-OC16 provide?

Isolation is 75V continuous, I/O to system, tested to 1900V DC for 1 s, I/O to system; there is no isolation between individual channels.

What external fusing is recommended for the 1794-OC16?

A 2 A, 150V AC MQ2 normal fuse is recommended; module outputs are not fused, and external fusing is strongly recommended.

Voltage, on-state output, nom
48V DC, sourcing
Voltage, on-state output, min
30V DC
Voltage, on-state output, max
60V DC @ 45 °C; 55V DC @ 55 °C
Voltage drop, on-state output, max
1.0V DC @ 0.5 A
Terminal base unit
1794-TB2, 1794-TB3, 1794-TB3S, 1794-TB3K, 1794-TB3SK
Current, on-state output, min
2.0 mA per channel
Current, on-state output, max
500 mA per channel; 8 A per module
Leakage current,
1.0 mA
Output surge current, max
4 A for 10 ms, repeatable every 2 s
Output delay time, OFF to ON, max
0.5 ms
Output delay time, ON to OFF, max
1.0 ms @ 25 °C; 2.0 ms @ 55 °C
External DC supply voltage range
30…60V DC (5% ripple)
External DC supply current range
13…27 mA
Power dissipation, max
3.7 W @ 60V DC
Thermal dissipation, max
12.6 BTU/hr @ 60V DC
Dimensions (HxWxD), approx
46 x 94 x 53 mm (1.8 x 3.7 x 2.1 in); 94 x 94 x 69 mm (3.7 x 3.7 x 2.7 in) installed
Isolation voltage
75V continuous, I/O to system; tested to 1900V DC for 1 s, I/O to system; no isolation between individual channels
Temperature, operating
0…55 °C (32…131 °F)
Recommended external fusing
2 A, 150V AC MQ2 normal fuse (module outputs are not fused; external fusing is strongly recommended)

Technical specifications are based on the linked manufacturer reference.

Unmatched Customer Service

After Hours Shipping

Real Time Order Tracking

Flexible Delivery Options

Intact Technical Supports

What Does Our Clients Say

Mitsubishi MR-J4

Laura Navas

Great product!

2019/12/01

Keyence sensor

EQDR SALES

Original and fast!

2020/02/22

Need Professional Tech Support or a Quote?

  • Our senior engineers provide 1-on-1 selection & configuration advice
  • 100% genuine products guaranteed with rapid global delivery
UP
WhatsApp