1794-IF4I Procurement Questions
What input signal ranges does the 1794-IF4I support?
It measures input voltage in the ±10V range or input current in the 0…20 mA range, and each channel is individually configurable for the desired input range.
What types of field devices can be connected to this module?
It is used with 2-, 3-, and 4-wire input sensor field devices.
What overload can a single channel withstand?
Voltage input max overload is 30V, single channel, continuous; current input max overload is 32 mA, single channel, continuous.
What is the input resistance, and does it change if module power is removed?
Current input resistance is less than 100 Ω and voltage input resistance is more than 10 MΩ; if 24V DC is removed from the module, input resistance = 10 kΩ.
What accuracy is specified and at what temperature?
Current input: 0.1% Full Scale @ 25 °C (77 °F); voltage input: 0.1% Full Scale @ 25 °C (77 °F).
What data formats and conversion type does the module use?
Data formats are 2's complement, 2's complement percent, binary, and offset binary; the input conversion type is Sigma Delta.
- Input signal ranges
- Channel-to-channel isolated input module; measures input voltage in ±10V range or input current in the 0…20 mA range; each channel individually configurable; use with 2-, 3-, and 4-wire input sensor field devices
- Voltage, input, max overload
- 30V, single channel, continuous
- Current, input, max overload
- 32 mA, single channel, continuous
- Input resolution
- 16 bits unipolar; 15 bits + sign bipolar; 0.320 μA/cnt unipolar; 0.640 μA/cnt bipolar; 0.156 mV/cnt unipolar; 0.313 mV/cnt bipolar
- Input resistance
- Current input: <100 Ω; voltage input: >10 MΩ
- Input resistance with 24V DC removed
- 10 kΩ
- Data format
- 2's complement; 2's complement percent; binary; offset binary
- Input conversion type
- Sigma Delta
- Input conversion rate
- 2.5/5.0/7.5 ms all channels
- Normal mode rejection ratio
- -3 dB @ 12 Hz (300 Hz conversion rate); -80.0 dB @ 50 Hz (300 Hz conversion rate)
- Calibration
- Factory calibrated
- Step response to 63% of FS, input
- Current or voltage input: 1200 Hz conversion rate = 0.6 ms; 600 Hz conversion rate = 6.7 ms; 300 Hz conversion rate = 13.4 ms; 150 Hz conversion rate = 26.7 ms
- Dimensions (HxWxD), approx
- 46 x 94 x 53 mm (1.8 x 3.7 x 2.1 in); 94 x 94 x 69 mm (3.7 x 3.7 x 2.7 in) installed
- Resolution
- 16 bit unipolar; 15 bit + bipolar
- Accuracy
- Current input: 0.1% Full Scale @ 25 °C (77 °F); voltage input: 0.1% Full Scale @ 25 °C (77 °F)
- Temperature, operating
- 0…55 °C (32…131 °F)
Technical specifications are based on the linked manufacturer reference.