1794-IR8 Procurement Questions
Which RTD types and temperature ranges does the 1794-IR8 support?
The module accepts 2- and 3-wire RTDs, and the published sensor list covers 100 Ω Pt μ = 0.00385 Euro (-200…+870 °C), 100 Ω Pt μ = 0.003916 U.S. (-200…+630 °C), 200 Ω Pt μ = 0.00385 Euro (-200…+630 °C), 500 Ω Pt μ = 0.00385 U.S. (-200…+630 °C), 100 Ω Nickel μ = 0.00618 (-60…+250 °C), 120 Ω Nickel μ = 0.00672 (-60…+250 °C), 200 Ω Nickel μ = 0.00618 (-60…+250 °C), 500 Ω Nickel μ = 0.00618 (-60…+250 °C) and 10 Ω Copper μ = 0.00427 (-200…+260 °C).
What accuracy can I expect without calibration?
Accuracy, normal mode (max) is 0.05% Full Scale (low humidity) without calibration, and accuracy, enhanced mode (typical) is 0.01% Full Scale (low humidity) without calibration.
How fast does the module update channels?
System throughput in normal mode is programmable from 28…325 ms/channel; 325 ms (1 channel scanned); 2.6 s (8 channels scanned). In enhanced mode it is programmable from 56…650 ms/channel; 650 ms (1 channel scanned); 2.925 s (8 channels scanned).
How does the module behave when an RTD is open?
Open RTD detection is reported as an out of range upscale reading.
What overvoltage can the inputs withstand?
Overvoltage capability is 35V DC, 25V AC continuous @ 25 °C, plus 250V peak transient.
What are the mounting dimensions and operating temperature?
Dimensions (HxWxD), approx are 46 x 94 x 53 mm (1.8 x 3.7 x 2.1 in); 94 x 94 x 69 mm (3.7 x 3.7 x 2.7 in) installed, and operating temperature is -20…+55 °C (-4…+131 °F).
- RTD wiring
- Temperature-measuring module that accepts 2- and 3-wire RTDs
- Input resolution
- 16 bits across 435 Ω
- Sensors supported
- 100 Ω Pt μ = 0.00385 Euro (-200…+870 °C); 100 Ω Pt μ = 0.003916 U.S. (-200…+630 °C); 200 Ω Pt μ = 0.00385 Euro (-200…+630 °C); 500 Ω Pt μ = 0.00385 U.S. (-200…+630 °C); 100 Ω Nickel μ = 0.00618 (-60…+250 °C); 120 Ω Nickel μ = 0.00672 (-60…+250 °C); 200 Ω Nickel μ = 0.00618 (-60…+250 °C); 500 Ω Nickel μ = 0.00618 (-60…+250 °C); 10 Ω Copper μ = 0.00427 (-200…+260 °C)
- Data format
- 16 bits, 2's complement, left justified; offset binary
- Settling time
- 100% of final value available at system throughput rate
- Normal mode rejection ratio
- 60 dB @ 60 Hz for A/D filter cutoff @ 15 Hz
- Common mode rejection ratio
- -120 dB @ 60 Hz; -100 dB @ 50 Hz with A/D filter cutoff @ 10 Hz
- Common mode voltage
- 0V between channels (common return)
- Accuracy, normal mode (max)
- 0.05% Full Scale (low humidity) without calibration
- Accuracy, enhanced mode (typical)
- 0.01% Full Scale (low humidity) without calibration
- System throughput, normal mode
- Programmable from 28…325 ms/channel; 325 ms (1 channel scanned); 2.6 s (8 channels scanned)
- System throughput, enhanced mode
- Programmable from 56…650 ms/channel; 650 ms (1 channel scanned); 2.925 s (8 channels scanned)
- Open RTD detection
- Out of range upscale reading
- Overvoltage capability
- 35V DC, 25V AC continuous @ 25 °C; 250V peak transient
- Channel bandwidth
- DC to 2.62 Hz (-3 dB)
- RTD excitation current
- 718.39 μA
- RFI immunity
- Error of <1% of range @ 10V/m, 27…1000 MHz
- Gain drift with temperature
- Normal mode: 20 ppm/°C max; enhanced mode: 10 ppm/°C max
- Dimensions (HxWxD), approx
- 46 x 94 x 53 mm (1.8 x 3.7 x 2.1 in); 94 x 94 x 69 mm (3.7 x 3.7 x 2.7 in) installed
- Temperature, operating
- -20…+55 °C (-4…+131 °F)