1794-IRT8 Procurement Questions
Which input types does the 1794-IRT8 accept?
It accepts thermocouple inputs, 2-, 3-, and 4-wire RTD inputs, and mV source inputs.
What is needed when using the module in thermocouple mode?
Use cold junction compensators 1794-CJC2 in thermocouple mode; two cold junction compensators are shipped with the module.
What accuracy does the module provide in mV mode?
Accuracy is 0.05% of full range in mV mode with filtering selected; hardware only: 0.10% of full range in mV mode.
How does the module behave on an open input?
Series A: RTD and TC modes — open input — module defaults to max value; Series B: RTD mode — open input — module defaults to max value; Series B: TC mode — open input — module defaults to min value.
What overvoltage capability applies, and under what condition?
Series A: 7V DC continuous @ 25 °C; Series B: 15V DC continuous @ 25 °C.
What is the cold junction compensation range for each firmware series?
0…70 °C for firmware Series A revision D or earlier; -20…100 °C for firmware Series A revision E or later; -20…100 °C for firmware Series B.
- Input types
- Accepts thermocouple inputs, 2-, 3-, and 4-wire RTD inputs, and mV source inputs
- Cold junction compensators
- Use cold junction compensators 1794-CJC2 in thermocouple mode; two cold junction compensators are shipped with the module
- Input resolution
- 14 bits
- Supported RTD types
- 100 Ω Pt μ = 0.00385 Euro (-200…+870 °C); 100 Ω Pt μ = 0.003916 U.S. (-200…+630 °C); 200 Ω Pt μ = 0.00385 Euro (-200…+400 °C); 200 Ω Pt μ = 0.003916 U.S. (-200…+400 °C); 100 Ω Nickel μ = 0.00618 (-60…+250 °C); 120 Ω Nickel μ = 0.00672 (-60…+320 °C); 200 Ω Nickel μ = 0.00618 (-60…+200 °C); 10 Ω Copper μ = 0.00427 (-200…+260 °C)
- Supported thermocouple types
- Type B: 300…1800 °C (572…3272 °F); Type E: -270…+1000 °C (-454…+1832 °F); Type J: -210…+1200 °C (-346…+2192 °F); Type K: -270…+1372 °C (-454…+2502 °F); Type N: -270…+1300 °C (-454…+2372 °F); Type R: -50…+1768 °C (-58…+3214 °F); Type S: -50…+1768 °C (-58…+3214 °F); Type T: -270…+400 °C (-454…+752 °F); Type TXK/XK (L): -200…+800 °C (-328…+1472 °F)
- Accuracy
- 0.05% of full range in mV mode with filtering selected; hardware only: 0.10% of full range in mV mode
- Common mode rejection ratio
- -80 dB @ 5V peak-to-peak 50…60 Hz
- Common mode input range
- Series A: ±4V; Series B: ±15V
- System throughput
- 7.4 ms mV; 8.0 ms Ω 2-wire; 10.0 ms Ω 3-wire; 10.4 ms Ω 4-wire; 8.0 ms Ω 2-wire RTD (°F); 10.4 ms Ω 4-wire RTD (°F); 8.8 ms Ω 2-wire RTD (°C), (°K); 10.8 ms Ω 4-wire RTD (°C), (°K); 9.8 ms Ω 3-wire RTD (°F); 10.0 ms Ω 3-wire RTD (°C), (°K); 8.0 ms thermocouples (°F); 8.8 ms thermocouples (°C), (°K)
- Open circuit detection type
- Series A: RTD and TC modes — open input — module defaults to max value; Series B: RTD mode — open input — module defaults to max value; Series B: TC mode — open input — module defaults to min value
- Excitation current
- 630 μA
- Overvoltage capability
- Series A: 7V DC continuous @ 25 °C; Series B: 15V DC continuous @ 25 °C
- Open input detection time
- 0…3.8 s for Series A revision D or earlier; immediate detection (max 2 scans) for Series A revision E or later; immediate detection (max 2 scans) for Series B
- Cold junction compensation range
- 0…70 °C for firmware Series A revision D or earlier; -20…100 °C for firmware Series A revision E or later; -20…100 °C for firmware Series B
- Cold junction compensation
- A-B Cold Junction Compensation Kit, 1794-CJC