Allen-Bradley 1794-IRT8 FLEX I/O Thermocouple/RTD Input Module

Series#: AllenBradley

Product Details

  • Allen-Bradley 1794-IRT8 FLEX I/O Thermocouple/RTD Input Module
  • Input channels: 8
  • Input device types: Thermocouples, 2-wire/3-wire/4-wire RTDs and mV sources
  • Cold junction compensation: 1794-CJC2 compensators in thermocouple mode

Specification

Allen-Bradley 1794-IRT8 FLEX I/O Thermocouple/RTD Input Module.

Technical Specifications

SpecificationDetails
ManufacturerAllen-Bradley
Catalog number1794-IRT8
Input channels8
Input device typesThermocouples, 2-wire/3-wire/4-wire RTDs and mV sources
Cold junction compensation1794-CJC2 compensators in thermocouple mode
Grounded thermocouplesGrounded thermocouple capability is identified for Series B

1794-IRT8 Procurement Questions

Which input types does the 1794-IRT8 accept?

It accepts thermocouple inputs, 2-, 3-, and 4-wire RTD inputs, and mV source inputs.

What is needed when using the module in thermocouple mode?

Use cold junction compensators 1794-CJC2 in thermocouple mode; two cold junction compensators are shipped with the module.

What accuracy does the module provide in mV mode?

Accuracy is 0.05% of full range in mV mode with filtering selected; hardware only: 0.10% of full range in mV mode.

How does the module behave on an open input?

Series A: RTD and TC modes — open input — module defaults to max value; Series B: RTD mode — open input — module defaults to max value; Series B: TC mode — open input — module defaults to min value.

What overvoltage capability applies, and under what condition?

Series A: 7V DC continuous @ 25 °C; Series B: 15V DC continuous @ 25 °C.

What is the cold junction compensation range for each firmware series?

0…70 °C for firmware Series A revision D or earlier; -20…100 °C for firmware Series A revision E or later; -20…100 °C for firmware Series B.

Input types
Accepts thermocouple inputs, 2-, 3-, and 4-wire RTD inputs, and mV source inputs
Cold junction compensators
Use cold junction compensators 1794-CJC2 in thermocouple mode; two cold junction compensators are shipped with the module
Input resolution
14 bits
Supported RTD types
100 Ω Pt μ = 0.00385 Euro (-200…+870 °C); 100 Ω Pt μ = 0.003916 U.S. (-200…+630 °C); 200 Ω Pt μ = 0.00385 Euro (-200…+400 °C); 200 Ω Pt μ = 0.003916 U.S. (-200…+400 °C); 100 Ω Nickel μ = 0.00618 (-60…+250 °C); 120 Ω Nickel μ = 0.00672 (-60…+320 °C); 200 Ω Nickel μ = 0.00618 (-60…+200 °C); 10 Ω Copper μ = 0.00427 (-200…+260 °C)
Supported thermocouple types
Type B: 300…1800 °C (572…3272 °F); Type E: -270…+1000 °C (-454…+1832 °F); Type J: -210…+1200 °C (-346…+2192 °F); Type K: -270…+1372 °C (-454…+2502 °F); Type N: -270…+1300 °C (-454…+2372 °F); Type R: -50…+1768 °C (-58…+3214 °F); Type S: -50…+1768 °C (-58…+3214 °F); Type T: -270…+400 °C (-454…+752 °F); Type TXK/XK (L): -200…+800 °C (-328…+1472 °F)
Accuracy
0.05% of full range in mV mode with filtering selected; hardware only: 0.10% of full range in mV mode
Common mode rejection ratio
-80 dB @ 5V peak-to-peak 50…60 Hz
Common mode input range
Series A: ±4V; Series B: ±15V
System throughput
7.4 ms mV; 8.0 ms Ω 2-wire; 10.0 ms Ω 3-wire; 10.4 ms Ω 4-wire; 8.0 ms Ω 2-wire RTD (°F); 10.4 ms Ω 4-wire RTD (°F); 8.8 ms Ω 2-wire RTD (°C), (°K); 10.8 ms Ω 4-wire RTD (°C), (°K); 9.8 ms Ω 3-wire RTD (°F); 10.0 ms Ω 3-wire RTD (°C), (°K); 8.0 ms thermocouples (°F); 8.8 ms thermocouples (°C), (°K)
Open circuit detection type
Series A: RTD and TC modes — open input — module defaults to max value; Series B: RTD mode — open input — module defaults to max value; Series B: TC mode — open input — module defaults to min value
Excitation current
630 μA
Overvoltage capability
Series A: 7V DC continuous @ 25 °C; Series B: 15V DC continuous @ 25 °C
Open input detection time
0…3.8 s for Series A revision D or earlier; immediate detection (max 2 scans) for Series A revision E or later; immediate detection (max 2 scans) for Series B
Cold junction compensation range
0…70 °C for firmware Series A revision D or earlier; -20…100 °C for firmware Series A revision E or later; -20…100 °C for firmware Series B
Cold junction compensation
A-B Cold Junction Compensation Kit, 1794-CJC

Technical specifications are based on the linked manufacturer reference.

Unmatched Customer Service

After Hours Shipping

Real Time Order Tracking

Flexible Delivery Options

Intact Technical Supports

What Does Our Clients Say

Mitsubishi MR-J4

Laura Navas

Great product!

2019/12/01

Keyence sensor

EQDR SALES

Original and fast!

2020/02/22

Need Professional Tech Support or a Quote?

  • Our senior engineers provide 1-on-1 selection & configuration advice
  • 100% genuine products guaranteed with rapid global delivery
UP
WhatsApp