Allen-Bradley 1794-IT8 FLEX I/O Thermocouple/mV Input Module

Series#: AllenBradley

Product Details

  • Allen-Bradley 1794-IT8 FLEX I/O Thermocouple/mV Input Module
  • Input channels: 8
  • Input signal range: Thermocouples and mV sources in the ±76.5 mV range
  • Cold junction compensation: 1794-CJC2 compensators in thermocouple mode

Specification

Allen-Bradley 1794-IT8 FLEX I/O Thermocouple/mV Input Module.

Technical Specifications

SpecificationDetails
ManufacturerAllen-Bradley
Catalog number1794-IT8
Input channels8
Input signal rangeThermocouples and mV sources in the ±76.5 mV range
Cold junction compensation1794-CJC2 compensators in thermocouple mode

1794-IT8 Procurement Questions

What input range does the 1794-IT8 accept from a mV source?

The module accepts mV source inputs in the range of ±76.5 mV, and it also accepts inputs from a variety of thermocouples, grounded or ungrounded.

Which thermocouple types can the 1794-IT8 measure, and over what ranges?

Type B: 300…1800 °C (572…3272 °F); Type C: 0…2315 °C (32…4199 °F); Type E: -270…+1000 °C (-454…+1832 °F); Type J: -210…+1200 °C (-346…+2192 °F); Type K: -270…+1372 °C (-454…+2502 °F); Type N: -270…+1300 °C (-454…+2372 °F); Type R: -50…+1768 °C (-58…+3214 °F); Type S: -50…+1768 °C (-58…+3214 °F); Type T: -270…+400 °C (-454…+752 °F); Type TXK/XK (L): -200…+800 °C (-328…+1472 °F).

Is cold junction compensation supplied with the module?

Yes. A-B Cold Junction Compensation Kit 1794-CJC is specified, and cold junction compensator kit 1794-CJC2 (two compensators) is included with the module. The cold junction compensation range is 0…70 °C.

How does the module report an open input?

Open input detection is available at system throughput rate, and the open circuit detection type is an out of range reading (upscale).

What accuracy and drift figures apply to the 1794-IT8?

With filter (max) accuracy is 0.025% Full Scale @ 24 °C (±0.5 °C); without filter (max) it is 0.05% Full Scale @ 24 °C (±0.5 °C). Input offset drift with temperature is +6 μV/°C max, gain drift with temperature max is 10 ppm/°C, and overall drift with temperature max is 50 ppm/°C of span.

What are the system throughput and operating temperature of the 1794-IT8?

System throughput is 325 ms (1 channel scanned), programmable to 28 ms, and 2.6 s (8 channels scanned), programmable to 224 ms. Operating temperature is -20…+55 °C (-4…+131 °F).

mV input range
Temperature/mV measuring module; mV source input range ±76.5 mV; supports grounded or ungrounded thermocouples
Cold junction compensators
Cold junction compensator kit 1794-CJC2 (two compensators) is included with the module
Input resolution
16 bits (2.384 μV typical)
Supported thermocouple types
Type B: 300…1800 °C (572…3272 °F); Type C: 0…2315 °C (32…4199 °F); Type E: -270…+1000 °C (-454…+1832 °F); Type J: -210…+1200 °C (-346…+2192 °F); Type K: -270…+1372 °C (-454…+2502 °F); Type N: -270…+1300 °C (-454…+2372 °F); Type R: -50…+1768 °C (-58…+3214 °F); Type S: -50…+1768 °C (-58…+3214 °F); Type T: -270…+400 °C (-454…+752 °F); Type TXK/XK (L): -200…+800 °C (-328…+1472 °F)
Data format
16 bits, 2's complement; offset binary (unipolar)
Settling time
100% of final value available at system throughput rate
Normal mode rejection ratio
60 dB @ 60 Hz
Common mode rejection ratio
-115 dB @ 60 Hz; -100 dB @ 50 Hz
Common mode input range
±10V
Accuracy
With filter (max): 0.025% Full Scale @ 24 °C (±0.5 °C); without filter (max): 0.05% Full Scale @ 24 °C (±0.5 °C)
System throughput
325 ms (1 channel scanned), programmable to 28 ms; 2.6 s (8 channels scanned), programmable to 224 ms
Open input detection
Available at system throughput rate
Open circuit detection type
Out of range reading (upscale)
Overvoltage capability
35V DC, 25V AC continuous @ 25 °C; 250V peak transient
Channel bandwidth
0…2.62 Hz (-3 dB)
RFI immunity
Error of <1% of range @ 10V/m, 27…1000 MHz
Input offset drift with temperature
+6 μV/°C max
Gain drift with temperature, max
10 ppm/°C
Overall drift with temperature, max
50 ppm/°C of span
Cold junction compensation range
0…70 °C
Cold junction compensation
A-B Cold Junction Compensation Kit, 1794-CJC
Dimensions (HxWxD), approx
46 x 94 x 53 mm (1.8 x 3.7 x 2.1 in); 94 x 94 x 69 mm (3.7 x 3.7 x 2.7 in) installed
Temperature, operating
-20…+55 °C (-4…+131 °F)

Technical specifications are based on the linked manufacturer reference.

Unmatched Customer Service

After Hours Shipping

Real Time Order Tracking

Flexible Delivery Options

Intact Technical Supports

What Does Our Clients Say

Mitsubishi MR-J4

Laura Navas

Great product!

2019/12/01

Keyence sensor

EQDR SALES

Original and fast!

2020/02/22

Need Professional Tech Support or a Quote?

  • Our senior engineers provide 1-on-1 selection & configuration advice
  • 100% genuine products guaranteed with rapid global delivery
UP
WhatsApp