1794-IE4XOE2 Procurement Questions
What input and output ranges can be configured on the 1794-IE4XOE2?
The input current terminal is user configurable for 4…20 mA or 0…20 mA, and the input voltage terminal for +10V or 0…10V. The output current terminal offers 4…20 mA or 0…20 mA, and the output voltage terminal +10V or 0…10V.
How is the module isolated?
Isolation voltage is tested at 850V DC for 1 s between user power to system; there is no isolation between individual channels.
What supply voltage and current does the module require?
External DC power supply voltage, nom, is 24V DC, with a range of 10.5…31.2V DC (includes 5% AC ripple). External DC power supply current is 165 mA @ 24V DC, and Flexbus current is 15 mA.
What load can the current output drive?
The 1794-IN100D publication states a resistive load on the mA output of 15…750 Ω @ 24V DC; the selection guide table prints 15…750 Ω without a supply-voltage condition.
What overload can a voltage input withstand?
The selection guide table gives voltage input overload, max, as 30V, single channel, continuous; 1794-IN100D gives maximum overload, one channel at a time, as 30V continuous or 32 mA continuous.
What are the conversion rates and step responses?
Input conversion rate is 256 μs all channels and output conversion rate is 1.024 ms all channels. Step response to 63% of FS is 18.2 ms for current input and 9.4 ms for voltage input, and 24 ms for current or voltage output.
- Calibration
- None required
- Input conversion type
- Successive approximation
- Input conversion rate
- 256 μs all channels
- Input resolution
- 12 bits unipolar; 11 bits + sign bipolar; 5.13 μA/cnt; 2.56 μV/cnt unipolar; 5.13 μV/cnt bipolar
- Data format
- 16 bits, 2's complement; left-justified
- Step response to 63% of FS, input
- Current input: 18.2 ms; voltage input: 9.4 ms
- Step response to 63% of FS, output
- Current or voltage output: 24 ms
- Normal mode rejection ratio
- Current input: -3 dB @ 9 Hz, -20 dB/decade, -15.3 dB @ 50 Hz, -16.8 dB @ 60 Hz; voltage input: -3 dB @ 17 Hz, -20 dB/decade, -10 dB @ 50 Hz, -11.4 dB @ 60 Hz
- Accuracy
- Current input: 0.20% Full Scale @ 25 °C; voltage input: 0.20% Full Scale @ 25 °C; current output: 0.425% Full Scale @ 25 °C; voltage output: 0.133% Full Scale @ 25 °C
- Accuracy drift with temperature
- Current input: 0.0407% Full Scale @ 25 °C; voltage input: 0.0428% Full Scale @ 25 °C; current output: 0.0069% Full Scale @ 25 °C; voltage output: 0.0045% Full Scale @ 25 °C
- Input impedance
- Current input: 238 Ω; voltage input: 100 kΩ
- Voltage input, overload, max
- 30V, single channel, continuous
- Output resolution
- 12 bits + sign; 5.13 μA/cnt; 2.56 mV/cnt
- Output conversion type
- Pulse width modulation
- Output conversion rate
- 1.024 ms all channels
- Current load on voltage output, max
- 3 mA
- Resistive load on current output
- 15…750 Ω
- Dimensions (HxWxD), approx
- 46 x 94 x 53 mm (1.8 x 3.7 x 2.1 in); 94 x 94 x 69 mm (3.7 x 3.7 x 2.7 in) installed
- Temperature, operating
- -20…+55 °C (-4…+131 °F)
- Number of inputs, single-ended, nonisolated (1794-IN100D)
- 4
- Number of outputs, single-ended, nonisolated (1794-IN100D)
- 2
- Resolution, inputs (1794-IN100D)
- 12 bits unipolar; 11 bits plus sign bipolar; voltage: 2.56 mV/cnt unipolar, 5.13 mV/cnt bipolar; current: 5.13 µA/cnt
- Resolution, outputs (1794-IN100D)
- 12 bits plus sign; voltage: 0.156 mV/cnt; current: 0.320 µA/cnt
- Input current terminal, user configurable (1794-IN100D)
- 4…20 mA; 0…20 mA
- Input voltage terminal, user configurable (1794-IN100D)
- +10V; 0…10V
- Output current terminal, user configurable (1794-IN100D)
- 4…20 mA; 0…20 mA
- Output voltage terminal, user configurable (1794-IN100D)
- +10V; 0…10V
- Input resistance, voltage terminal (1794-IN100D)
- Voltage terminal: 200 kΩ; current terminal: 238 Ω
- Accuracy drift with temperature, inputs (1794-IN100D)
- Voltage terminal: 0.00428% full-scale/°C; current terminal: 0.00407% full-scale/°C
- Accuracy drift with temperature, outputs (1794-IN100D)
- Voltage terminal: 0.0045% full-scale/°C; current terminal: 0.0069% full-scale/°C
- Maximum overload, one channel at a time (1794-IN100D)
- 30V continuous or 32 mA continuous
- Resistive load on mA output (1794-IN100D)
- 15…750 Ω @ 24V DC
- Recommended terminal base unit (1794-IN100D)
- 1794-TB2, 1794-TB3, 1794-TB3S, 1794-TB3T, and 1794-TB3TS
- Keyswitch position (1794-IN100D)
- 5
- External DC power supply current (1794-IN100D)
- 165 mA @ 24V DC
- Power dissipation, max (1794-IN100D)
- 4.0 W @ 31.2V DC
- Thermal dissipation, max (1794-IN100D)
- 15.3 BTU/hr @ 31.2V DC
- North American temp code (1794-IN100D)
- T4A
- External DC power supply voltage, nom (1794-IN100D)
- 24V DC
- External DC power supply voltage range (1794-IN100D)
- 10.5…31.2V DC (includes 5% AC ripple)
- Flexbus current (1794-IN100D)
- 15 mA
- Isolation voltage (1794-IN100D)
- Tested at 850V DC for 1 s between user power to system; no isolation between individual channels
- Dimensions, approx (1794-IN100D)
- 45.7 x 94 x 53.3 mm (1.8 x 3.7 x 2.1 in) with module installed
- Temperature, operating (1794-IN100D)
- -20…+55 °C (-4…+131 °F)
- Temperature, storage (1794-IN100D)
- –40…+85 °C (–40…+185 °F)