1794-IF2XOF2I Procurement Questions
What isolation voltage does this module provide?
Isolation voltage is 120V continuous when used with 1794-TB3, 1794-TB3S, 1794-TB2, 1794-TB3T, or 1794-TB3TS, and 250V continuous when used with 1794-TBN; it is tested at 1500V AC for 60 s and 2550V DC for 1 s, channel to channel, I/O to system.
What input conversion rate and resolution are specified?
The input conversion rate is 2.5/5.0/7.5 ms all channels, and input resolution is 16 bit unipolar and 15 bit + sign bipolar, with 0.156 mV/cnt unipolar, 0.313 mV/cnt bipolar, 0.320 μA/cnt unipolar and 0.640 μA/cnt bipolar.
What is the step response to 63% of full scale on the input?
For current or voltage input: 1200 Hz conversion rate = 0.6 ms; 600 Hz conversion rate = 6.7 ms; 300 Hz conversion rate = 13.4 ms; 150 Hz conversion rate = 26.7 ms.
What loads can the outputs drive?
The maximum current load on voltage output is 3 mA, and the resistive load on current output is 0…750 Ω.
What are the module dimensions and operating temperature?
Dimensions are approximately 46 x 94 x 53 mm (1.8 x 3.7 x 2.1 in), or 94 x 94 x 69 mm (3.7 x 3.7 x 2.7 in) installed; operating temperature is -20…+55 °C (-4…+131 °F).
How does accuracy drift with temperature?
Accuracy drift with temperature is: current input 0.0038% Full Scale/°C; voltage input 0.0028% Full Scale/°C; current output 0.0025% Full Scale/°C; voltage output 0.0012% Full Scale/°C.
- Calibration
- Factory calibration
- Input conversion type
- Sigma Delta
- Input conversion rate
- 2.5/5.0/7.5 ms all channels
- Input resolution
- 16 bit unipolar; 15 bit + sign bipolar; 0.156 mV/cnt unipolar; 0.313 mV/cnt bipolar; 0.320 μA/cnt unipolar; 0.640 μA/cnt bipolar
- Isolation voltage
- 120V continuous (when used with 1794-TB3, 1794-TB3S, 1794-TB2, 1794-TB3T, or 1794-TB3TS); 250V continuous (when used with 1794-TBN); tested at 1500V AC for 60 s and 2550V DC for 1 s, channel to channel, I/O to system
- Data format
- 16 bits, 2's complement; 2's complement percent; binary; offset binary
- Step response to 63% of FS, input
- Current or voltage input: 1200 Hz conversion rate = 0.6 ms; 600 Hz conversion rate = 6.7 ms; 300 Hz conversion rate = 13.4 ms; 150 Hz conversion rate = 26.7 ms
- Normal mode rejection ratio
- -3 dB @ 12 Hz (300 Hz conversion rate); -80.0 dB @ 50 Hz (300 Hz conversion rate); -3 dB at 6 Hz (150 Hz conversion rate); -80 dB at 60 Hz (150 Hz conversion rate)
- Accuracy
- Current input or output: 0.1% Full Scale @ 25 °C; voltage input or output: 0.1% Full Scale @ 25 °C
- Accuracy drift with temperature
- Current input: 0.0038% Full Scale/°C; voltage input: 0.0028% Full Scale/°C; current output: 0.0025% Full Scale/°C; voltage output: 0.0012% Full Scale/°C
- Input impedance
- Current input: <100 Ω; voltage input: >1 MΩ
- Input resistance with 24V DC removed
- 10 kΩ
- Voltage input, overload, max
- 30V, single channel, continuous
- Output resolution
- 15 bit + sign; 0.656 μA/cnt; 0.320 mV/cnt
- Output conversion type
- Digital-to-analog converter
- Output conversion rate
- 2.5/5.0 ms
- Current load on voltage output, max
- 3 mA
- Resistive load on current output
- 0…750 Ω
- Dimensions (HxWxD), approx
- 46 x 94 x 53 mm (1.8 x 3.7 x 2.1 in); 94 x 94 x 69 mm (3.7 x 3.7 x 2.7 in) installed
- Temperature, operating
- -20…+55 °C (-4…+131 °F)