1794-OF4I Procurement Questions
What output types and signal ranges does the 1794-OF4I support?
It provides 4 isolated outputs for 2-, 3-, and 4-wire output devices that use voltage in the range of ±10V or 0…20 mA current.
Which terminal base should I use if I need 250V continuous isolation?
Isolation voltage is 120V (continuous) when used with 1794-TB2, 1794-TB3, 1794-TB3S, 1794-TB3T, or 1794-TB3TS, and 250V (continuous) when used with 1794-TBN; the module is type tested at 1500V AC for 60 s and 2550V DC for 1 s, channel to channel, I/O to system.
What load can the current output drive?
Output current with resistive load is 0…750 Ω, and the maximum current load on the voltage output is 3 mA.
How accurate is the module and how does accuracy change with temperature?
Accuracy is 0.1% Full Scale @ 25 °C (77 °F) for current and 0.1% Full Scale @ 25 °C (77 °F) for voltage; accuracy drift with temperature is 0.0025% Full Scale/°C for current and 0.0012% Full Scale/°C for voltage.
What wire size and wire category apply to the field wiring?
Wire size is 0.34…2.5 mm2 (22...12 AWG) solid or stranded shielded copper wire rated at 75 °C (167 °F) or greater, with 1.2 mm (3/64 in.) insulation max; wire category is 2 on signal ports and 3 on power ports.
What is the operating temperature range and the module dimensions?
Operating temperature is -20…+55 °C (-4…+131 °F); approximate dimensions are 46 x 94 x 53 mm (1.8 x 3.7 x 3.1 in), or 94 x 94 x 69 mm (3.7 x 3.7 x 2.7 in) installed.
- Channel configuration
- 4 isolated outputs for 2-, 3-, and 4-wire output devices that use voltage in the range of ±10V or 0…20 mA current
- Output resolution
- 15 bit + sign; 0.656 μA/cnt; 0.320 mV/cnt
- Data format
- 2's complement; 2's complement percent; binary; offset binary
- Output conversion type
- Digital to analog converter
- Output conversion rate
- 2.5/5.0 ms
- Step response to 63% of FS, output
- Current or voltage output: <25 μs
- Current load on voltage output, max
- 3 mA
- Output current, resistive load
- 0…750 Ω
- Accuracy
- Current: 0.1% Full Scale @ 25 °C (77 °F); voltage: 0.1% Full Scale @ 25 °C (77 °F)
- Accuracy drift with temperature
- Current: 0.0025% Full Scale/°C; voltage: 0.0012% Full Scale/°C
- Calibration
- Factory calibrated
- Isolation voltage
- 120V (continuous) when used with 1794-TB2, 1794-TB3, 1794-TB3S, 1794-TB3T, or 1794-TB3TS; 250V (continuous) when used with 1794-TBN; type tested at 1500V AC for 60 s and 2550V DC for 1 s, channel to channel, I/O to system
- Power dissipation, max
- 4.7 W @ 31.2V DC
- Thermal dissipation, max
- 16 BTU/hr @ 31.2V DC
- Wire size
- 0.34…2.5 mm2 (22...12 AWG) solid or stranded shielded copper wire rated at 75 °C (167 °F) or greater; 1.2 mm (3/64 in.) insulation max
- Wire category
- 2 – on signal ports; 3 – on power ports
- Dimensions (HxWxD), approx
- 46 x 94 x 53 mm (1.8 x 3.7 x 3.1 in); 94 x 94 x 69 mm (3.7 x 3.7 x 2.7 in) installed
- Temperature, operating
- -20…+55 °C (-4…+131 °F)
Technical specifications are based on the linked manufacturer reference.