1794-IJ2 Procurement Questions
What types of sensors can the 1794-IJ2 frequency inputs accept?
The frequency inputs accept a 24V DC IEC1+ proximity switch as defined by standard IEC 1131-2, a 24V DC contact switch with wire-off capability, 500 mV AC magnetic pickup, 50 mV AC magnetic pickup, 6V AC vortex, and 3V AC vortex.
What input frequency range does the module support?
Input frequency, max is 1…32 kHz with sine wave input and 1…32 kHz with square wave input.
What supply voltage does the module require?
Customer supplied power ranging from 10…31.2V DC is connected internally.
How much current can each output source, and what happens on overload?
Current, on-state output, max is 1.0 A per channel sourced out of module; output Q1 is a thermally protected FET that turns off at 3 A (approximately), and after a thermal shutdown the cause must be fixed and the outputs toggled ON and OFF to re-energize the output.
What are the module dimensions?
Dimensions (HxWxD), approx are 46 x 94 x 53 mm (1.8 x 3.7 x 3.1 in), and 94 x 94 x 69 mm (3.7 x 3.7 x 2.7 in) installed.
What is the operating temperature range for this model?
Temperature, operating for 1794-IJ2 is -20…+55 °C (-4…+131 °F).
- Module function
- Tachometer-style intelligent I/O module reporting frequency, acceleration, and direction; outputs are activated by alarms; the module provides 2 frequency inputs, 2 gate inputs, and 2 outputs; frequency inputs accept frequencies up to 32 kHz
- Accepted frequency inputs
- 24V DC IEC1+ proximity switch as defined by standard IEC 1131-2; 24V DC contact switch with wire-off capability; 500 mV AC magnetic pickup; 50 mV AC magnetic pickup; 6V AC vortex; 3V AC vortex
- Accepted gate inputs
- 24V DC IEC1+ proximity switch as defined by standard IEC 1131-2; 24V DC contact switch; 500 mV AC magnetic pickup; 50 mV AC magnetic pickup
- Customer supplied power
- 10…31.2V DC
- Output thermal protection
- Thermally protected FET output turns off at 3 A (approximately); after a thermal shutdown, fix the cause and toggle the outputs ON and OFF to re-energize the output
- Isolated sensor power supply
- 1 isolated 24V DC power supply providing 2 current-limited outputs of 30 mA maximum (1 for each channel)
- Processing time
- ≤4 ms
- Input frequency, max
- 1…32 kHz with sine wave input; 1…32 kHz with square wave input
- Frequency value, max
- 32,767 or 3,276.7 (dependent on range)
- Input pulse width, min
- 20 μs
- Voltage, on-state input, min
- 10V (24V IEC+1 proximity, encoder input or switch inputs)
- Voltage, on-state input, nom
- 24V DC
- Voltage, on-state input, max
- Limited to isolated 24V DC power supply
- Current, on-state input, min
- 2.0 mA
- Current, on-state input, nom
- 9.0 mA
- Current, on-state input, max
- 10.0 mA
- Voltage, off-state input, max
- 5.0V DC
- Current, off-state input, max
- 1.5 mA
- Wire-off detection
- 0.4 mA for proximity, encoder, or contact switch with 50 kΩ shunt resistor
- Impedance, frequency input
- >5 kΩ for 50 mV extended magnetic pickup; >5 kΩ for 500 mV magnetic pickup; >10 kΩ for 3V vortex flowmeter; >10 kΩ for 6V vortex flowmeter; >2.5 kΩ for 24V DC IEC1+ proximity or encoder input; >2.5 kΩ for 24V DC contact switch input
- Impedance, gate input
- >5 kΩ for 50 mV extended magnetic pickup; >5 kΩ for 500 mV magnetic pickup; >2.5 kΩ for 24V DC IEC1+ proximity or encoder input; >2.5 kΩ for 24V DC contact switch input
- Output voltage source
- Customer supplied
- Voltage, on-state output, min
- 10V DC
- Voltage, on-state output, nom
- 24V DC
- Voltage, on-state output, max
- 31.2V DC
- Current, on-state output, min
- 1.0 mA per output
- Current, on-state output, max
- 1.0 A per channel sourced out of module
- Output surge current, max
- 2 A for 50 ms, repeatable every 2 s
- Voltage drop, on-state output, max
- 0.9V DC @ 1 A
- Output control
- Outputs individually assignable to: frequency; % full scale; acceleration alarm
- Output switching time
- Triggered by frequency alarm or acceleration alarm; turn on: <0.5 ms; turn off: <1 ms
- Dimensions (HxWxD), approx
- 46 x 94 x 53 mm (1.8 x 3.7 x 3.1 in); 94 x 94 x 69 mm (3.7 x 3.7 x 2.7 in) installed
- Temperature, operating
- -20…+55 °C (-4…+131 °F)
Technical specifications are based on the linked manufacturer reference.