Allen-Bradley 1794-IJ2 FLEX I/O Frequency Input Module

Series#: AllenBradley

Product Details

  • Allen-Bradley 1794-IJ2 FLEX I/O Frequency Input Module
  • Input/output configuration: 2 frequency inputs, 2 gate inputs and 2 outputs
  • Maximum frequency input: 32 kHz
  • Input device examples: Magnetic pickup, flowmeter, incremental encoder and proximity detector; use the listed signal ratings

Specification

Allen-Bradley 1794-IJ2 FLEX I/O Frequency Input Module.

Technical Specifications

SpecificationDetails
ManufacturerAllen-Bradley
Catalog number1794-IJ2
Input/output configuration2 frequency inputs, 2 gate inputs and 2 outputs
Maximum frequency input32 kHz
Input device examplesMagnetic pickup, flowmeter, incremental encoder and proximity detector; use the listed signal ratings

1794-IJ2 Procurement Questions

What types of sensors can the 1794-IJ2 frequency inputs accept?

The frequency inputs accept a 24V DC IEC1+ proximity switch as defined by standard IEC 1131-2, a 24V DC contact switch with wire-off capability, 500 mV AC magnetic pickup, 50 mV AC magnetic pickup, 6V AC vortex, and 3V AC vortex.

What input frequency range does the module support?

Input frequency, max is 1…32 kHz with sine wave input and 1…32 kHz with square wave input.

What supply voltage does the module require?

Customer supplied power ranging from 10…31.2V DC is connected internally.

How much current can each output source, and what happens on overload?

Current, on-state output, max is 1.0 A per channel sourced out of module; output Q1 is a thermally protected FET that turns off at 3 A (approximately), and after a thermal shutdown the cause must be fixed and the outputs toggled ON and OFF to re-energize the output.

What are the module dimensions?

Dimensions (HxWxD), approx are 46 x 94 x 53 mm (1.8 x 3.7 x 3.1 in), and 94 x 94 x 69 mm (3.7 x 3.7 x 2.7 in) installed.

What is the operating temperature range for this model?

Temperature, operating for 1794-IJ2 is -20…+55 °C (-4…+131 °F).

Module function
Tachometer-style intelligent I/O module reporting frequency, acceleration, and direction; outputs are activated by alarms; the module provides 2 frequency inputs, 2 gate inputs, and 2 outputs; frequency inputs accept frequencies up to 32 kHz
Accepted frequency inputs
24V DC IEC1+ proximity switch as defined by standard IEC 1131-2; 24V DC contact switch with wire-off capability; 500 mV AC magnetic pickup; 50 mV AC magnetic pickup; 6V AC vortex; 3V AC vortex
Accepted gate inputs
24V DC IEC1+ proximity switch as defined by standard IEC 1131-2; 24V DC contact switch; 500 mV AC magnetic pickup; 50 mV AC magnetic pickup
Customer supplied power
10…31.2V DC
Output thermal protection
Thermally protected FET output turns off at 3 A (approximately); after a thermal shutdown, fix the cause and toggle the outputs ON and OFF to re-energize the output
Isolated sensor power supply
1 isolated 24V DC power supply providing 2 current-limited outputs of 30 mA maximum (1 for each channel)
Processing time
≤4 ms
Input frequency, max
1…32 kHz with sine wave input; 1…32 kHz with square wave input
Frequency value, max
32,767 or 3,276.7 (dependent on range)
Input pulse width, min
20 μs
Voltage, on-state input, min
10V (24V IEC+1 proximity, encoder input or switch inputs)
Voltage, on-state input, nom
24V DC
Voltage, on-state input, max
Limited to isolated 24V DC power supply
Current, on-state input, min
2.0 mA
Current, on-state input, nom
9.0 mA
Current, on-state input, max
10.0 mA
Voltage, off-state input, max
5.0V DC
Current, off-state input, max
1.5 mA
Wire-off detection
0.4 mA for proximity, encoder, or contact switch with 50 kΩ shunt resistor
Impedance, frequency input
>5 kΩ for 50 mV extended magnetic pickup; >5 kΩ for 500 mV magnetic pickup; >10 kΩ for 3V vortex flowmeter; >10 kΩ for 6V vortex flowmeter; >2.5 kΩ for 24V DC IEC1+ proximity or encoder input; >2.5 kΩ for 24V DC contact switch input
Impedance, gate input
>5 kΩ for 50 mV extended magnetic pickup; >5 kΩ for 500 mV magnetic pickup; >2.5 kΩ for 24V DC IEC1+ proximity or encoder input; >2.5 kΩ for 24V DC contact switch input
Output voltage source
Customer supplied
Voltage, on-state output, min
10V DC
Voltage, on-state output, nom
24V DC
Voltage, on-state output, max
31.2V DC
Current, on-state output, min
1.0 mA per output
Current, on-state output, max
1.0 A per channel sourced out of module
Output surge current, max
2 A for 50 ms, repeatable every 2 s
Voltage drop, on-state output, max
0.9V DC @ 1 A
Output control
Outputs individually assignable to: frequency; % full scale; acceleration alarm
Output switching time
Triggered by frequency alarm or acceleration alarm; turn on: <0.5 ms; turn off: <1 ms
Dimensions (HxWxD), approx
46 x 94 x 53 mm (1.8 x 3.7 x 3.1 in); 94 x 94 x 69 mm (3.7 x 3.7 x 2.7 in) installed
Temperature, operating
-20…+55 °C (-4…+131 °F)

Technical specifications are based on the linked manufacturer reference.

Unmatched Customer Service

After Hours Shipping

Real Time Order Tracking

Flexible Delivery Options

Intact Technical Supports

What Does Our Clients Say

Mitsubishi MR-J4

Laura Navas

Great product!

2019/12/01

Keyence sensor

EQDR SALES

Original and fast!

2020/02/22

Need Professional Tech Support or a Quote?

  • Our senior engineers provide 1-on-1 selection & configuration advice
  • 100% genuine products guaranteed with rapid global delivery
UP
WhatsApp