Allen-Bradley 1794-VHSC FLEX I/O Very High-Speed Counter Module

Series#: AllenBradley

Product Details

  • Allen-Bradley 1794-VHSC FLEX I/O Very High-Speed Counter Module
  • Encoder interfaces: 2 incremental quadrature encoder interfaces, each with A, B and Z inputs
  • Maximum frequency without filters: 1.0 MHz for counter/encoder X1; 500 kHz for X2; 250 kHz for X4
  • Outputs: 2 configurable outputs

Specification

Allen-Bradley 1794-VHSC FLEX I/O Very High-Speed Counter Module.

Technical Specifications

SpecificationDetails
ManufacturerAllen-Bradley
Catalog number1794-VHSC
Encoder interfaces2 incremental quadrature encoder interfaces, each with A, B and Z inputs
Maximum frequency without filters1.0 MHz for counter/encoder X1; 500 kHz for X2; 250 kHz for X4
Outputs2 configurable outputs
External power supply24V external supply

1794-VHSC Procurement Questions

What encoder and pulse inputs does the 1794-VHSC provide?

It has two incremental quadrature encoder interfaces, each with three inputs (A, B, and Z), and ± inputs for connection to pulse transmitters with complementary or non-complementary signals.

What is the maximum input frequency and how does the edge multiplier affect it?

The maximum input frequency is 1.0 MHz for counter and encoder X1 (no filters), 500 kHz for encoder X2 (no filters), and 250 kHz for encoder X4 (no filters).

What input filter selections are available?

Five selections per A/B/Z group: Off, 10 μs, 100 μs, 1.0 ms, and 10.0 ms.

What are the on-state and off-state input voltage thresholds?

For 5V DC terminations, on-state input min is >2.6V DC and off-state input min is ≤1.25V DC; for 15…24V DC terminations, on-state input min is >12.5V DC and off-state input min is ≤1.8V DC.

What output supply voltage range and output current ratings apply?

The output supply voltage range is 5…7V DC or 10…31V DC. Current, on-state output, max is 5V operation – 0.5 A and 12…24V operation – 1.0 A; current per output pair, max is 5V operation – 0.9 A and 12…24V operation – 4.0 A.

What are the output delay times?

Output delay time OFF to ON is 25 μs (load dependent) and ON to OFF is 150 μs (load dependent).

Counter interfaces
Two incremental quadrature encoder interfaces, each with three inputs (A, B, and Z); ± inputs for connection to pulse transmitters with complementary or non-complementary signals
Counter registers and limits
Up/down counting with detection of a selectable number of edges (X1, X2, X4); each counter has an upper limit of 1 MHz, a 24-bit counter register, a preset register, and a latch register; two outputs configurable for overlapping, multiple windows, and/or pulse-width modulation
Input groups
2 groups of A/A, B/B, and Z/Z pairs with 5V DC or 15…24V DC terminations
Input frequency, max
1.0 MHz counter and encoder X1 (no filters); 500 kHz encoder X2 (no filters); 250 kHz encoder X4 (no filters)
Voltage, on-state input, min
5V DC terminations: >2.6V DC; 15…24V DC terminations: >12.5V DC
Voltage, on-state input, max
5V DC terminations: ±6V; 15…24V DC terminations: refer to derating curve
Voltage, off-state input, min
5V DC terminations: ≤1.25V DC; 15…24V DC terminations: ≤1.8V DC
Current, on-state input, min
>5 mA
Current, on-state input, max
≤0.250 mA
Input filter selections
Off, 10 μs, 100 μs, 1.0 ms, 10.0 ms per A/B/Z group (5 selections)
Output control
Outputs can be tied to 8 compare windows
Output supply voltage range
5…7V DC or 10…31V DC
Leakage current, off-state output, max
≤0.3 mA
Voltage drop, on-state output, max
5V operation – 0.5 A; 12…24V operation – 1.0 A
Current, on-state output, max
5V operation – 0.5 A; 12…24V operation – 1.0 A
Current per output pair, max
5V operation – 0.9 A; 12…24V operation – 4.0 A
Short circuit current
5V operation – 0.9V DC @ 0.5 A; 12…24V operation – 0.9V DC @ 1.0 A
Output delay time, OFF to ON
25 μs (load dependent)
Output delay time, ON to OFF
150 μs (load dependent)
Dimensions (HxWxD), approx
46 x 94 x 53 mm (1.8 x 3.7 x 3.1 in); 94 x 94 x 69 mm (3.7 x 3.7 x 2.7 in) installed
Temperature, operating
0…55 °C (32…131 °F)

Technical specifications are based on the linked manufacturer reference.

Unmatched Customer Service

After Hours Shipping

Real Time Order Tracking

Flexible Delivery Options

Intact Technical Supports

What Does Our Clients Say

Mitsubishi MR-J4

Laura Navas

Great product!

2019/12/01

Keyence sensor

EQDR SALES

Original and fast!

2020/02/22

Need Professional Tech Support or a Quote?

  • Our senior engineers provide 1-on-1 selection & configuration advice
  • 100% genuine products guaranteed with rapid global delivery
UP
WhatsApp